BMTZY - NP SERIES LEAD/ACID BATTERY
- MSDS: BMTZY
- Manufacturer: YUASA EXIDE INC
- Product Name: NP SERIES LEAD/ACID BATTERY
- National Stock Number: 6135-01-272-4048
Product Identification
Product ID:NP SERIES LEAD/ACID BATTERY
MSDS Date:01/02/1991
FSC:6135
NIIN:01-272-4048
MSDS Number: BMTZY
Responsible Party
READING, PA 19605-9607
US
Emergency Phone: 610-208-1991/610-208-1975
Info Phone: 610-208-1991/610-208-1975
Cage: IO592
Contractor
Telephone: 610-208-1975
Cage: IO592
Ingredients
SULFURIC ACID (SARA III)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: 32-40%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3; 9192
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
LEAD (BATTERY INTERNALS OF LEAD) (SARA III)
CAS: 7439-92-1
RTECS: OF7525000
OSHA PEL 0.05 MG/M3;1910.1025
ACGIH TLV: 0.15 MG/M3;DUST 9192
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
Hazards
LD50 LC50 Mixture:ORAL RAT LD50 IS NOT KNOWN
Routes of Entry: Inhalation:NO Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:NO
Health Hazards Acute and Chronic:PRODUCT CONTAINS LEAD AND SULFURIC
ACID. SULFURIC ACID IS A CORROSIVE CAUSING BURNS TO BODY TISSUES.
LEAD IS TOXIC AND SOME LEAD COMPOUNDS ARE LISTED AS CARCINOGENIC.
CONTACT WITH EITHER IS HIGHLY UNLIKELY TO OCCUR UNLESS THE CASE IS
BROKEN OR SPILLED, THEN ONLY CONTACT WITH THE ACID IS LIKELY.
Explanation of Carcinogenicity:LEAD COMPOUNDS ARE LISTED AS
CARCINOGENIC IN ANIMALS AND POSSILBY IN HUMANS.
Effects of Overexposure:CONTACT WITH SULFURIC ACID IS THE MOST LIKELY
EXPOSURE, PRODUCING IRRITATION OR BURNS TO THE BODY TISSUE
CONTACTED.
Medical Cond Aggravated by Exposure:NONE
First Aid
First Aid:FIRST AID IS GIVEN FOR SULFURIC ACID CONTACT. EYE:FLUSH
W/WATER 15 MIN, HOLD LIDS OPEN. SKIN:WASH WITH SOAP & WATER.
REMOVE CONTAMINATED CLOTHING AND LAUNDER BEFORE REUSE.
INHALED:REMOVE TO FRESH A IR. INGESTED:DO NOT INDUCE VOMITING.
GIVE 2 LARGE GLASSES OF MILK OR WATER AND GET IMMEDIATE MEDICAL
CARE. GIVE NOTHING BY MOUTH IF UNCONSCIOUS. IF IRRITATION
PERSISTS OR IS SEVERE,SEE A DOCTOR.
Fire Fighting
Flash Point:NON-FLAMMABLE
Extinguishing Media:USE WATER FOG, CARBON DIOXIDE, FOAM, OR DRY
CHEMICAL.
Fire Fighting Procedures:WEAR ACID RESISTANT PROTECTIVE EQUIPMENT AND A
FULL FACED SELF CONTAINED BREATHING APPARATUS. COOL FIRE EXPOSED
CONTAINERS WITH WATER SPRAY.
Unusual Fire/Explosion Hazard:WHEN BEING CHARGED THIS BATTERY GENERATES
HYDROGEN GAS WHICH MAY FORM EXPLOSIVE MIXTURES WITH AIR.
ELECTROLYTE REACTS WITH WATER OR WITH METALS TO RELEASE H*2.
Accidental Release
Spill Release Procedures:IF ACID IS SPILLED, NEUTRALIZE. PLACE
REMAINDER IN AN ACID RESISTANT CONTAINER FOR RECYCLE OF THE LEAD.
Neutralizing Agent:SODIUM BICARBONATE OR LIME
Handling
Handling and Storage Precautions:STORE IN COOL, DRY AREA. PROTECT FROM
PHYSICAL DAMAGE. PROTECT TERMINALS FROM SHORT CIRCUITS.
Other Precautions:READ MANUFACTURERS LITERATURE AND FOLLOW
INSTRUCTIONS.
Exposure Controls
Respiratory Protection:RESPIRATOR WILL NOT NORMALLY BE NECESSARY. USE
NIOSH/MSHA APPROVED RESPIRATOR FOR ACID DUST/MIST IF EXPOSURE IS
ABOVE THE TLV/PEL. SEE 29 CFR 1910.134 FOR REGULATIONS PERTAINING
TO RESPIRATOR USE.
Ventilation:NOT NORMALLY REQUIRED. USE LOCAL EXHAUST DURING CHARGING
CYCLES TO AVOID AN EXPLOSIVE BUILD UP OF HYDROGEN GAS.
Protective Gloves:NONE (RUBBER IF ACID IS LEAKING)
Eye Protection:SAFETY GLASSES/SPLASH GOGGLES FOR LIQUID
Other Protective Equipment:NORMAL WORK CLOTHING. PROTECT WITH
IMPERVIOUS APRON AND/OR BOOTS WHEN HANDLING ACID OR IF ACID IS
LEAKING.
Work Hygienic Practices:USE GOOD INDUSTRIAL HYGIENE PRACTICE. AVOID
ALL CONTACT WITH ACID OR INTERNALS OF THE BATTERY.
Supplemental Safety and Health
NON-SPILLABLE BATTERY, PER CTDF.
Chemical Properties
HCC:N1
Boiling Pt:B.P. Text:203F,95C
Vapor Pres:10 MM
Vapor Density:>1
Spec Gravity:1.27
Solubility in Water:100%
Appearance and Odor:COLORLESS,TRANSPARENT, ONO ODOR (NOTE DESCRIPTION
OF ELECTROLYTE NOT BATTERY)
Stability
Stability Indicator/Materials to Avoid:YES
COMBUSTIBLES, ORGANIC MATERIALS, STRONG REDUCING AGENTS, METALS,
CYANIDES.
Stability Condition to Avoid:RUPTURE OF BATTERY CASE.
Hazardous Decomposition Products:CHARGING, ESPECIALLY OVERCHARGING
RELEASES HYDROGEN, A FLAMMABLE EXPLOSIVE GAS.
Disposal
Waste Disposal Methods:DISPOSE I/A/W ALL FEDERAL, STATE AND LOCAL
REGULATIONS. HMIS SUGGESTS THAT DISPOSAL MAY BE DONE BY FLUSHING
NEUTRALIZED ACID TO DRAIN AND SENDING REMAINDER TO LEAD RECLAIMER.
DO NOT INCINERATE!!!
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.